APPLICATION: DISCONNECT SWITCHES IN MV TRANSFORMATION CENTERS | Model No: NP-0650 10KVA DC-UPS with Input – Output Ground |
---|---|
GENERAL FEATURES: Uninterruptible Power Supply DC and high isolation with dual output. This product is designed for charging 48V batteries between 12 and 18Ah. It has an end of life battery alarm. This is done by taking eriodic measurements of the impedance of the battery during its life. AC input voltage: 230VAC AC input voltage range: 184 280VAC Starting inrush current: Efficiency: 85% Output voltage: 54,4Vdc / 12VDC Output current: 3,5A / 10A Output peak current: 6A / 10A Operating temperature range: -25...65ºC Format: Subrack 19” 3U |
![]() |
APPLICATION: RECLOSERS, SWITCH DISCONNECTORS | Model No: NP-0715 350W Triple Output 250Watts Peak Charge Rectifier |
GENERAL FEATURES: UPS DC for batteries of 12V and 38Ah with Ethernet communications. The product has an end of life battery alarm. The system detects and adapts automatically to any type of Pb battery. A temperature sensor adjusts the floating voltage to optimize the battery life. Mains input voltage: 230VAC Mains voltage range: -15%...+20% Mains frequency range: 47...63Hz Inrush current: < 12A 3 Output: This email address is being protected from spambots. You need JavaScript enabled to view it. (26A peak 10ms), This email address is being protected from spambots. You need JavaScript enabled to view it. (5.2A peak 10ms), This email address is being protected from spambots. You need JavaScript enabled to view it. Operating temperature range: -25...60°C |
![]() |
APPLICATION: DISCONNECT SWITCHES WITH MOTORIZED OPERATION FOR MV LINES | Model No: NP-0660 DC UPS 12V |
GENERAL FEATURES: UPS DC for batteries of 12V and 30 to 40Ah. The product has an end of life battery alarm. The system detects and adapts automatically to any type of Pb battery. A temperature sensor adjusts the floating voltage to optimize the battery life. Mains voltage: Universal Mains voltage range: 99 290.4VAC Mains frequency range: 47...63Hz Power factor: > 0.95 Inrush current: < 18A Efficiency: > 80% Nominal output voltage: 13.6V Maximum continuous current: 4A Maximum peak current: 30A (10s) Operating temperature range:-25...70°C |
![]() |
APPLICATION: PHOTOVOLTAICS | Model No: NP-0567 & NP-0583 3KVA (6KVA PEAK) Inverter with 24V / 48Vin |
GENERAL FEATURES: Nominal output voltage: 230VAC (50/60HZ) configurable by software Nominal output power: 3000VA Max. Output power transient: 6000VA (9 seconds) Input voltage margin: 20 to 31VDC / 40 to 62Vdc (2 models) Stand-by operation: Adjustable from 0 to 230W Stand-by consumption: <100mA Efficiency: >91% RS232 port to send display information, alarms and remote control |
![]() |
APPLICATION: AUTOMATED TRANSFORMER SUBSTATIONS | Model No: NP-0716 48VDC 400W Peak Charger Rectifier |
GENERAL FEATURES: UPS DC for batteries of 48V and 10...20Ah with Ethernet communications. The product has an end of life battery alarm. The system detects and adapts automatically to any type of Pb battery. A temperature sensor adjusts the floating voltage to optimize the battery life. Mains input voltage: 230VAC Mains voltage range: -15%...+20% Mains frequency range: 47...63Hz Inrush current: < 20A Output voltage: 48V Maximum continuous current (Io): 5.2A Maximum peak current (10s): 10.3A Operating temperature range: -25...60°C |
![]() |
APPLICATION: DATA COMMUNICATION OVER HIGH VOLTAGE LINES | Model No: NP-0604 Triple Output 82Watts DC-DC Converter |
GENERAL FEATURES: Input voltage: 48VDC Input voltage range: 36 ... 72VDC Maximum ripple: < 5% (CEI870-2-1) Inrush current: < 10A 3 Output: 3.3V@10A, 5V@5A, 12V@2A |
![]() |